Braemar Compatibility: SDHV series inverter ducted, single phase units onlySDHV07D1S / SCHV07D1S ( 7kW ) |
SERIES & kW | INDOOR | OUTDOOR |
SINGLE PHASE / 7kw - 16kw | SDHV##D1S | SCHV##D1S |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Current Firmware Version - 1.3 |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Can use RA as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Cannot use Zones, Master or RF as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Polarity is critical see below, for correct connection |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Requires Braemar proprietary controller for setup |
Connect the Braemar proprietary wired controller to the FCU PCB
Enter the service mode parameters
To enter Service Mode, power must be connected to the unit and proprietary wired controller, and the unit must be switched 'OFF' at the wall control. Follow the steps below and refer to the function and parameter setting table
3. As per the instructions set the sensor to return air for all modes
4. Set the iZone control setting
5. Set the required static pressure setting
6. Cycle the power to the AC unit
7. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
A connector and short cable has been provided with the C325B but will need to be extended |
Service Mode Parameter Table | |||||
Function Display | Function Description | Parameter Display | Parameter Description | ||
0 | Temp sensor location Ensure set to '01'
| 01 | Sensor at return air for all modes | ||
02 | Sensor at wired control for all modes | ||||
03 | Sensor at return air for cool, dry & fan modes, at wired control for heat mode | ||||
10 | iZone control Ensure set to '01' | 00 | Standard control | ||
01 | iZone control setting | ||||
11 | Indoor fan power setting Factory default '05' Adjust to suit installed static Low static = '01' High static = '09'
|
| ESP (Pa) | High Speed | Low Speed |
01 | 10 | 5 | 1 | ||
02 | 20 | 6 | 2 | ||
03 | 30 | 7 | 3 | ||
04 | 40 | 8 | 4 | ||
05 | 50 (default) | 9 | 5 | ||
06 | 75 | 10 | 6 | ||
07 | 100 | 11 | 7 | ||
08 | 150 | 12 | 8 | ||
09 | 200 | 13 | 9 |
1️⃣ Indoor fan coil unit PCB: Note connector CN1
2️⃣ Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical
3️⃣ C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
4️⃣ Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector
5️⃣ Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided