Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Actron Compatibility: Ultra Slim \ low profile series only LRE-071AS / URC-071AS ( 7kW ) LRE-100AS / URC-100AS ( 10kW ) LRE-130AS / URC-140AS (14kW ) |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Current Firmware Version - 1.3 |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Can use RA, Zones, Master and RF as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Polarity is critical see below, for correct connection |
Connect a shielded, 2 core, twisted pair control cable from the C225 / C325A to the X / Y in the fan coil unit. This cable and connector is supplied by iZone - CACUCM15
1️⃣ Indoor fan coil unit PCB
2️⃣ CN40: Connect to X and Y
3️⃣ C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
4️⃣ Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN40 connector on the fan coil PCB and the C225 cable connector
5️⃣ Cable from CN40: Ensure the cable is shielded, 2 core, twisted pair. This cable is pre-terminated suitable for CN40 connector and is supplied by iZone