Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Braemar Compatibility: SDHV series inverter ducted, single phase units only |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Current Firmware Version - 1.3 |
SERIES & kW | INDOOR | OUTDOOR |
SINGLE PHASE / 7kw - 16kw | SDHV##D1S KDHV##D1S | SCHV##D1S KCHV##D1B |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Can use RA as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Cannot use Zones, Master or RF as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Polarity is critical see below, for correct connection |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Requires Braemar proprietary controller for setup |
For SDHV07~16D1S:
For SDHV07~16D1S using XK60 or XK117 and KDHV070~160D1S using XE71 or XK75:
Unit in “OFF” state
Press “FUNCTION” & “TIMER” buttons for 5 seconds
Press “MODE” button to change “Function display” number
Press ▲ or ▼ button to change “Parameter display” number Press “ENTER/CANCEL” to save
For SDHV07~16D1S using XK75:
For KDHA series (GUD71~160PHS1/C-S) introduced late 2024:
No adjustments need.
3. As per the instructions set the sensor to return air for all modes
4. Set the iZone control setting
5. Set the required static pressure setting
6. Cycle the power to the AC unit
7. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
A connector and short cable has been provided with the C325B but will need to be extended |
Service Mode Parameter Table | |||||
Function Display | Function Description | Parameter Display | Parameter Description | ||
0 | Temp sensor location Ensure set to '01'
| 01 | Sensor at return air for all modes | ||
02 | Sensor at wired control for all modes | ||||
03 | Sensor at return air for cool, dry & fan modes, at wired control for heat mode | ||||
10 | iZone control Ensure set to '01' | 00 | Standard control | ||
01 | iZone control setting | ||||
11 | Indoor fan power setting Factory default '05' Adjust to suit installed static Low static = '01' High static = '09'
|
| ESP (Pa) | High Speed | Low Speed |
01 | 10 | 5 | 1 | ||
02 | 20 | 6 | 2 | ||
03 | 30 | 7 | 3 | ||
04 | 40 | 8 | 4 | ||
05 | 50 (default) | 9 | 5 | ||
06 | 75 | 10 | 6 | ||
07 | 100 | 11 | 7 | ||
08 | 150 | 12 | 8 | ||
09 | 200 | 13 | 9 |
1️⃣ Indoor fan coil unit PCB: Note connector CN1
2️⃣ Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical
3️⃣ C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
4️⃣ Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector
5️⃣ Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided