C325B

C325L2:

BRAEMAR

LG

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#B3D4FF

Braemar Compatibility: SDHV series inverter ducted, single phase units only

SDHV07D1S / SCHV07D1S ( 7kW )
SDHV10D1S / SCHV10D1S ( 10kW )
SDHV12D1S / SCHV12D1S ( 12kW )
SDHV14D1S / SCHV14D1S ( 14kW )
SDHV16D1S / SCHV16D1S ( 16kW )LG Compatibility: AWY-7G6 Series

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA as controlling sensor

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FFBDAD

Cannot use , Zones, Master or RF as controlling sensor

Panel
panelIconIdatlassian-warningcheck_mark
panelIcon:warningcheck_mark:
bgColor#FFF0B3#ABF5D1

Polarity is critical see below, for correct connection

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

Requires Braemar proprietary controller for setup

  1. Connect the Braemar proprietary wired controller to the FCU PCB

  2. Enter the service mode parameters

To enter Service Mode, power must be connected to the unit and proprietary wired controller, and the unit must be switched 'OFF' at the wall control. Follow the steps below and refer to the function and parameter setting table

Image Removed

3. As per the instructions set the sensor to return air for all modes

4. Set the iZone control setting

5. Set the required static pressure setting

6. Cycle the power to the AC unit

7. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit

not critical

  • Connect the LG supplied cable from the fan coil unit to the iZone C225 module Only use the black and yellow cables

Image Added
  1. Connect black and yellow wires only: Use the connector supplied with the LG unit to connect from the fan coil to the iZone C225. Only connect the black and yellow cables to the C225. Polarity is not critical

  2. LG control cable: Connect black and yellow cables only.

  3. Red cable not used: Red cable is not required for iZone connection

Image Added
Image Added

  • Indoor fan coil unit PCB: Note connector CN1

  • Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical

  • C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

  • Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector

  • Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided
    Panel
    panelIconIdatlassian-warningnote
    panelIcon:warningnote:
    bgColor#FFF0B3

    A connector and short cable has been provided with the C325B but will need to be extended

    Service Mode Parameter Table

    Function Display

    Function Description

    Parameter Display

    Parameter Description

    0

    Temp sensor location

    Ensure set to '01'

     

    01

    Sensor at return air for all modes

    02

    Sensor at wired control for all modes

    03

    Sensor at return air for cool, dry & fan modes, at wired control for heat mode

    10

    iZone control

    Ensure set to '01'

    00

    Standard control

    01

    iZone control setting

    11

    Indoor fan power setting

    Factory default '05'

    Adjust to suit installed static

    Low static = '01'

    High static = '09'

     

     

     

     

     

     

    ESP (Pa)

    High Speed

    Low Speed

    01

    10

    5

    1

    02

    20

    6

    2

    03

    30

    7

    3

    04

    40

    8

    4

    05

    50 (default)

    9

    5

    06

    75

    10

    6

    07

    100

    11

    7

    08

    150

    12

    8

    09

    200

    13

    9

    Image Removed
    Image Removed
    Image Removed
    #C0B6F2

    C325M2: MITSUBISHI ELECTRIC

    Panel
    panelIconIdatlassian-info
    panelIcon:info:
    bgColor#B3D4FF

    Mitsubishi Electric Compatibility:

    PE-M##GAA

    New MR Slim series (Must be C325M2)

    Panel
    panelIconIdatlassian-info
    panelIcon:info:
    bgColor#B3D4FF

    C320M & C325M have been superseded by C325M2

    Panel
    panelIconIdatlassian-check_mark
    panelIcon:check_mark:
    bgColor#ABF5D1

    Can use RA, Zones, Master or RF as controlling sensor

    Panel
    panelIconIdatlassian-check_mark
    panelIcon:check_mark:
    bgColor#ABF5D1

    Polarity is not critical

    • Take  the Remote Controller (A / B) control wire from the fan coil unit and connect it to the AC Unit Control Cable on the  C225 / C325M2

    Image Added
    1. Connect to A / B terminals: Connect wires to to A and B terminals. Polarity is not critical

    2. Mitsubishi Electric FCU PCB

    3. C225: iZone C225 module with C325M2 AC unit module connected

    4. Shielded, 2 Core, twisted pair: This cable is not provided by iZone