Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#B3D4FF

Daikin Compatibility: Will connect to most ducted models with a P1 / P2 terminal in the FCU and the current Daikin controller can run the unit

Info

Daikin Error Code Finder: https://www.daikin.com/products/ac/services/errorcode_search?lang=en

Info

Please see below for the instruction on how to connect and configure iZone with DAIKIN VRV.

Panel
panelIconIdatlassian-note
panelIcon:note:
bgColor#C0B6F2

Current Firmware Version - 1.2

...

#FFBDAD
Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Polarity is not critical

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor

Master/Slave options do not work with C325D2

...

1️⃣ P1 / P2: Connect to the P1 and P2 terminals in the Daikin FCU. Polarity is not critical

...

Info

DAIKIN VRV SET UP PROCEDURE BEFORE INSTALLING THE IZONE CONTROLLERS

 

Contractor to commission and run TEST mode on the Daikin VRV System as per Daikin’s standard procedure. During this process Daikin wired Controllers to be connected to EACH Fan Coil Unit.

 

  • After Commissioning, and test run / addressing procedures have been completed. Using the Daikin remote Controller for each Fan Coil Unit, set up Static pressures and other relevant parameters that are required for each Fan Coil Unit.

  • Once all the parameters have been set, one Remote Controller / Fan Coil Unit will have to be set as the Master or Primary Unit.  

  • Decide which Fan Coil Unit / Remote Controller will be the primary unit. Usually this will be the living area . This Fan Coil Unit / Remote Controller needs to be set as the Master or Primary.

  • All remote controllers should have this icon Flashing on top of the screen .VRV.pngImage Added

  • To set the Fan Coil Unit / Remote Controller as primary system ( Selection Eligibility) Press Mode once, this will turn on the back light, then press MODE Selector a second time. The ICON will disappear from the primary Remote controller. Once the Flashing ICON has disappeared from the remote Controller Screen means this remote is the Primary Controller.

  • The icon  will iconVRV.pngImage Added  will appear on the other remote controllers which denotes it is a secondary Controller. (See attached information on how to set Controller Eligibility)

  • Once the above Procedures have been completed ONLY then disconnect the Daikin Remote Controllers and install the iZone CPU and controllers.

  • If iZone Controllers are installed before the above procedures are completed, and the Daikin Remote Controllers are disconnected while the icon on icon VRV.pngImage Addedon each Remote controller is flashing. Then the Fan Coil Units will operate, However the condenser will not start.