Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

SERIES & kW

INDOOR

OUTDOOR

FDU Series

 

 

FDUA Series

 

 

FDUM Series

 

 

KX Series

 

 

FDC SERIES

FDC100VNP-W

Tip

Indoor models FDUA200VG, FDUA200VF and FDUA200VH are compatible.

Note

FDU280KXZE1 model is compatible with C325MHI v2.5 ONLY.

Note

Please be advised you may need to up the static pressure when installing MHI with iZONE. You will need to put the MHI controller on first and check the following setting.

 

  1. Input password in MHI controller ( 9999 )

  2. Go to installation set up

  3. Go to static pressure

  4. From factory will normally come set 80 pa to 100 pa, this setting may  cause outdoor unit not to fully cycle and the coil not to run correctly 

  5. Adjust to 160 pa and then run unit for 5 minutes

  6. Then disconnect and install iZone.

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA, Zones, Master or RF as controlling sensor

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Polarity is not critical

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

Please note master/slave options are not available on MHI units

  • Take the Remote Controller (X / Y) control wire from the fan coil unit and connect it to the AC Unit Control Cable on the  C225 / C325MHI2

...