LG Compatibility:

...

Panel
panelIconIdatlassian-

...

note
panelIcon:

...

note:
bgColor

...

Braemar Compatibility: SDHV series inverter ducted, single phase units only

...

#C0B6F2

Current Firmware Version - 1.0

SERIES & kW

INDOOR

OUTDOOR

 

B##AWYN7G6

 

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA

...

panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FFBDAD

...

, Zones, Master or RF as controlling sensor

Panel
panelIconIdatlassian-

...

check_mark
panelIcon:

...

check_mark:
bgColor

...

#ABF5D1

Polarity is

...

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

Requires Braemar proprietary controller for setup

  1. Connect the Braemar proprietary wired controller to the FCU PCB

  2. Enter the service mode parameters

To enter Service Mode, power must be connected to the unit and proprietary wired controller, and the unit must be switched 'OFF' at the wall control. Follow the steps below and refer to the function and parameter setting table

...

3. As per the instructions set the sensor to return air for all modes

4. Set the iZone control setting

5. Set the required static pressure setting

6. Cycle the power to the AC unit

7. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

A connector and short cable has been provided with the C325B but will need to be extended

...

Service Mode Parameter Table

...

Function Display

...

Function Description

...

Parameter Display

...

Parameter Description

...

0

Temp sensor location

Ensure set to '01'

 

...

01

...

Sensor at return air for all modes

...

02

...

Sensor at wired control for all modes

...

03

...

Sensor at return air for cool, dry & fan modes, at wired control for heat mode

...

10

iZone control

Ensure set to '01'

...

00

...

Standard control

...

01

...

iZone control setting

...

11

Indoor fan power setting

Factory default '05'

Adjust to suit installed static

Low static = '01'

High static = '09'

 

 

 

 

 

...

 

...

ESP (Pa)

...

High Speed

...

Low Speed

...

01

...

10

...

5

...

1

...

02

...

20

...

6

...

2

...

03

...

30

...

7

...

3

...

04

...

40

...

8

...

4

...

05

...

50 (default)

...

9

...

5

...

06

...

75

...

10

...

6

...

07

...

100

...

11

...

7

...

08

...

150

...

12

...

8

...

09

...

200

...

13

...

9

...

Image Removed
Image Removed

...

Indoor fan coil unit PCB: Note connector CN1

...

Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical

...

C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

...

Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector

...

not critical

  • Connect the LG supplied cable from the fan coil unit to the iZone C225 module Only use the black and yellow cables

...

1️⃣ Connect black and yellow wires only: Use the connector supplied with the LG unit to connect from the fan coil to the iZone C225. Only connect the black and yellow cables to the C225. Polarity is not critical

2️⃣ LG control cable: Connect black and yellow cables only.

3️⃣ Red cable not used: Red cable is not required for iZone connection