Kaden Compatibility:
KD24 ( 7.0 kW )
KD36 ( 10.5 kW )
KD42 ( 13.0 kW )
KD48 ( 14.5 kW )
KD60 ( 17.0 kW )
Current Firmware Version - 1.3
Can use RA, Zones, Master or RF as controlling sensor
Polarity is critical see below, for correct connection
Connect a 2 core + earth, twisted pair control cable from the C225 / C325KAD to the X / Y in the fan coil unit. This cable is supplied by iZone - CACUCM15
1️⃣ Indoor fan coil unit PCB
2️⃣ CN40: Connect to X and Y
3️⃣ C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
4️⃣ Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN40 connector on the fan coil PCB and the C225 cable connector
5️⃣ Cable from CN40: Ensure the cable is shielded, 2 core, twisted pair. This cable is pre-terminated suitable for CN40 connector and is supplied by iZone