Mitsubishi Heavy Industries Compatibility:

Current Firmware Version - 1.5

SERIES & kW

INDOOR

OUTDOOR

FDU Series

 

 

FDUA Series

 

 

FDUM Series

 

 

KX Series

 

 

Indoor models FDUA200VG, FDUA200VF and FDUA200VH are compatible.

  •  

Please be advised you may need to up the static pressure when installing MHI with iZONE. You will need to put the MHI controller on first and check the following setting.

 

  1. Input password in MHI controller ( 9999 )

  2. Go to installation set up

  3. Go to static pressure

  4. From factory will normally come set 80 pa to 100 pa, this setting may  cause outdoor unit not to fully cycle and the coil not to run correctly 

  5. Adjust to 160 pa and then run unit for 5 minutes

  6. Then disconnect and install iZone.

Can use RA, Zones, Master or RF as controlling sensor

Polarity is not critical

Please note master/slave options are not available on MHI units

  • Take the Remote Controller (X / Y) control wire from the fan coil unit and connect it to the AC Unit Control Cable on the  C225 / C325MHI2

1️⃣ Connect to X / Y terminals: Connect wires to X and Y terminals. Polarity is not critical

2️⃣ MHI FCU PCB

3️⃣ C225: iZone C225 module with C325MHI2 AC unit module connected

4️⃣ Shielded, 2 Core, twisted pair: This cable is not provided by iZone