Braemar Compatibility: SDHV series inverter ducted, single phase units only

Current Firmware Version - 1.3

SERIES & kW

INDOOR

OUTDOOR

SINGLE PHASE / 7kw - 16kw

SDHV##D1S 

KDHV##D1S

SCHV##D1S 

KCHV##D1B

Can use RA as controlling sensor

Cannot use Zones, Master or RF as controlling sensor

Polarity is critical see below, for correct connection

Requires Braemar proprietary controller for setup

For SDHV07~16D1S:

For SDHV07~16D1S using XK60 or XK117 and KDHV070~160D1S using XE71 or XK75:

Unit in “OFF” state
Press “FUNCTION” & “TIMER” buttons for 5 seconds
Press “MODE” button to change “Function display” number
Press ▲ or ▼ button to change “Parameter display” number Press “ENTER/CANCEL” to save

For SDHV07~16D1S using XK75:

XK75_steps.jpg

For KDHA series (GUD71~160PHS1/C-S) introduced late 2024:

No adjustments need.

3. As per the instructions set the sensor to return air for all modes

4. Set the iZone control setting

5. Set the required static pressure setting

6. Cycle the power to the AC unit

7. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit

A connector and short cable has been provided with the C325B but will need to be extended

Service Mode Parameter Table

Function Display

Function Description

Parameter Display

Parameter Description

0

Temp sensor location

Ensure set to '01'

 

01

Sensor at return air for all modes

02

Sensor at wired control for all modes

03

Sensor at return air for cool, dry & fan modes, at wired control for heat mode

10

iZone control

Ensure set to '01'

00

Standard control

01

iZone control setting

11

Indoor fan power setting

Factory default '05'

Adjust to suit installed static

Low static = '01'

High static = '09'

 

 

 

 

 

 

ESP (Pa)

High Speed

Low Speed

01

10

5

1

02

20

6

2

03

30

7

3

04

40

8

4

05

50 (default)

9

5

06

75

10

6

07

100

11

7

08

150

12

8

09

200

13

9

1️⃣ Indoor fan coil unit PCB: Note connector CN1

2️⃣ Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical

3️⃣ C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

4️⃣ Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector

5️⃣ Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided