Rinnai Compatibility:

Current Firmware Version - 1.0

SERIES & kW

INDOOR

OUTDOOR

DINLR XX Series only

 

 

Can use RA, Zones, Master or RF as controlling sensor

Polarity is critical see below, for correct connection

For CN40 connection.

CN40.jpgScreenshot 2024-02-15 155548.jpg

The new Rinnai indoor units may have either of two connections: CN9 and CNXYE.

For CN9 connection.

CN9.jpg

Screenshot 2024-02-15 155316.jpg

For CNXYE Connection

CNXYE.jpg7b50a67b-87fe-437a-a2bf-4828a1e50db1.jpg

(blue star) Indoor fan coil unit PCB

(blue star) CN40: Connect to X and Y

(blue star) C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

(blue star) Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN40 /CN9/CNXYE connector on the fan coil PCB and the C225 cable connector

(blue star) Cable from CN40: Ensure the cable is shielded, 2 core, twisted pair. This cable is pre-terminated suitable for CN40 connector and is supplied by iZone

Resetting the Unit Addressing on Rinnai 18Kw+ units

When a Rinnai AC unit controller is used to do a test run, to put the iZone control system back on and operate the AC, unit addressing needs to be reset. Below is the procedure on how to do it.

Off.png

 

image-20240823-022015.pngOn.png

 

Off.png

Dip switch ON-ON.png

IMG_3025.PNG