CPMK - Power Monitoring
PAGE CONTENTS
PHOTO & DESCRIPTION
Circuit being monitored: Active cable
CPMCT: iZone current transformer (CT)
Connector: The CT has a mail connector and the power monitoring device has a female connected. Unused female connectors have a weather proof plug. The connectors are used to enable the CT to be installed on a circuit inside a switch board or cabinet while the CPMD is installed out side the switchboard
CPMD: iZone power monitoring device
SPECIFICATIONS
Model numbers | CPMK | |
Certification | C Tick N29007 | |
Power supply | 2 x AA batteries | |
Connection | To be installed by a licenced electrician in accordance with AS/NZ 3000:2007 Electrical installations. | |
Measured current range | 20mA to 80Amp | |
Sensitivity | This device will measure in 1 Watt increments down to 5 Watts | |
Maximum connected load permitted | 5 Amp | |
Accuracy | This device is for monitoring only and is not recommended for calculation of actual power consumption. Accuracy can be up to 98% over an extended period but will vary as the batteries age and the "Power Factor" fluctuates at the site. | |
Control frequency | 433 MHz | |
Operating Temperature | -20oC to +50oC | |
Environment | Suitable for indoor or outdoor use. The CPMD must not be located inside a steel switch board or cabinet as this will prevent RF transmission of the data. | |
Limitations | Each CPMD can be fitted with up to 3 CPMCT and monitor 3 single phase circuits or one three phase circuit. A maximum of 5 CPMD devices can be installed on a single system. (15 x single phase circuits) | |
Requirements | An iZone bridge (COCB) and iZone World Wide account is required to view the iZone power monitoring system | |
Model number Height mm Width mm Depth mm Cable Diameter mm Weight g | CPMD 100 70 30 N/A 205 | CPMCT 46 30 30 15.5 90 |