C325HI - Haier R410 Gas Type
Current Firmware Version - 1.3
CODE | SENSOR TYPE | CONNECTION |
C325HI v1.3 | RA ONLY | A-B-C / Polarity Critical Requires proprietary controller / Requires Interface board |
SERIES & kW | INDOOR | OUTDOOR |
ADH Series only |
|
|
Can do Return Air ONLY - NOT Zones, Master or RF as controlling sensor.
Polarity is critical see below, for correct connection
Connect a shielded, 2 core, twisted pair control cable from the C225 / C325HI to the A / B terminals on the Haier Interface board YCJ-A002. Connect the interconnecting cable supplied by Haier to CN24 in the fan coil unit of the Haier Interface board YCJ-A002.
Set the dipswitches as shown below.
Haier Interface board YCJ-A002
Haier Interface Board Connections
Indoor Unit: ADH105H1ERG, ADH125H1ERG, ADH140H1ERG, ADH160H1ERG
Use CN24 connection
Indoor Unit: ADH200H1ERG, ADH250H1ERG
Use CN19 connection