Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
C325GC325P2:GREEPANASONIC |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Gree Panasonic Compatibility: Inverter ducted, single phase units only S - series units Nano X high static ducted units requires C325P2 |
Panel | ||||||||
---|---|---|---|---|---|---|---|---|
| Can use RA as controlling sensor
| |||||||
C320P & C325P have been superseded by C325P2 |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Cannot Can use RA, Zones, Master or RF as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Polarity is not critical see below, for correct connection |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Requires Gree proprietary controller for setup |
Connect the Gree proprietary wired controller to the FCU PCB
Enter the service mode parameters
To enter Service Mode, power must be connected to the unit and proprietary wired controller, and the unit must be switched 'OFF' at the wall control. Follow the steps below and refer to the function and parameter setting table
As per the instructions set the sensor to return air for all modes
Set the iZone control setting
Set the required static pressure setting
Cycle the power to the AC unit
Connect a 2 core, twisted pair control cable from the C225 / C325G X / Y to CN1 in the fan coil unit
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
A connector and short cable has been provided with the C325G but will need to be extended |
Service Mode Parameter Table
Function Display
Function Description
Parameter Display
Parameter Description
0
Temp sensor location
Ensure set to '01'
01
Sensor at return air for all modes
02
Sensor at wired control for all modes
03
Sensor at return air for cool, dry & fan modes, at wired control for heat mode
10
iZone control
Ensure set to '01'
00
Standard control
01
iZone control setting
11
Indoor fan power setting
Factory default '05'
Adjust to suit installed static
Low static = '01'
High static = '09'
ESP (Pa)
High Speed
Low Speed
01
10
5
1
02
20
6
2
03
30
7
3
04
40
8
4
05
50 (default)
9
5
06
75
10
6
07
100
11
7
08
150
12
8
09
200
13
9
Indoor fan coil unit PCB: Note connector CN1
Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical
C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector
Take the R1 / R2 control wire from the fan coil unit and connect it to the AC Unit Control Cable on the C225 / C325P2
C225 Module: Ensure a C325P / C325P2 module is connected to the C225 module
Connect R1 / R2 wires here: Use a shielded, 2 core, twisted pair cable from the FCU to the connector and short cable providedC225 module