If your Induct Temperature is showing displaying out-of-range temperatures like values, such as -90 degrees, or +90 degrees, etc. there could be a few reasons for that to happen, and can be rectified by following the steps below.

1️⃣ Check the placement:

Investigate and make sure that Induct sensor thermostat end is not touching any condensed water or interior part of the indoor coils as that can cause false data and display false may be several underlying causes. You can address this issue by following these steps:

  • Check the Placement:
    Ensure that the Induct sensor’s thermostat end is not in contact with any condensed water or the internal parts of the indoor coils. Such contact can lead to false data and inaccurate readings on the controller.

...

  • Replace the CDTS Sensor:
    If the sensor placement

...

  • is correct, the next step is to replace the CDTS

...

  • to

...

  • resolve the issue.

...

  • Change the CPU C225:
    If the

...

  • problem persists

...

  • even after replacing the sensor

...

  • ,

...

  • the

...

  • CDTS port

...

  • on the CPU may be causing the

...

  • inaccurate readings. In this case, we recommend

...

  • replacing the CPU to

...

  • rectify the issue.