OVERVIEW |
...
Zone temperature control requires the respective zones to be set to "Climate" and uses the iZone sensors to modulate the zone dampers to maintain the zone set point. Critical to the control of the zone temperatures is the supply air sensor (CDTS) which is used to invert the operation of the zone dampers when operating in heating and to avoid hot or cold air being blown into a zone when the the system first starts. The zone temperature control strategies use the following parameters for control:
As selected by the user
Panel |
---|
|
Zone Actual Temperature (ACT) |
As measured by the zone sensor. The displayed value takes into account any calibration offsets from the configuration menu
Panel |
---|
|
In Duct Temperature (SA) |
As measured by the CDTS sensor
Panel |
---|
|
Open - Zone damper is open to its maximum position after the MAX balancing % and user MAX Airflow % have been taken into account |
Panel |
---|
|
Close - Zone damper is closed to its minimum position after the MIN balancing % and user MIN Airflow % have been taken into account |
...