Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#B3D4FF

Fujitsu Compatibility:

Panel
panelIconIdatlassian-note
panelIcon:note:
bgColor#C0B6F2

Current Firmware Version - 1.11

SERIES & kW

INDOOR

OUTDOOR

ARTG Series Wiring: Connect AC control cable to 2 and 3 - Polarity IS Critical

High Static Single Phase - Compact Outdoor

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

 

High Static Single Phase

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

ARTG54LHTC

 

High Static Infinity Range - Single Phase ONLY

ARTG45LDTA (single phase)

ARTG54LDTA (single phase)

ARTG60LDTA (single phase)

 

High Static Three Phase

ARTC72LATU

ARTC90LATU

 

ARTH Series Wiring: Connect AC control cable to Y2-Y3 and SW1 dip switch ON - Polarity IS Critical

only compatible with C325F2

...

v1.11 module

High Static Single Phase

ARTH60KHTA ( Single Phase )

 

Standard Range

ARTH54KHTA (Single phase)

 

High Efficiency

ARTH60KHTB (Single phase)

 

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA, Zones, Master and RF as controlling sensor

Fujitsu Compatibility:

ARTC##LATU

ARTG##LHTA

ARTG60LDTA

ARTG24LHTDP

ARTC72/90 LATU
Panel
panelIconIdatlassian-infowarning
panelIcon:infowarning:
bgColor#B3D4FF
#FFF0B3

Polarity is critical see below, for correct connection

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FFBDAD

Do NOT use the terminal 1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  2 & 3 terminals in the Fujitsu FCU

...

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#B3D4FF

...

Fujitsu Compatibility:

ARTH60LHTA - ARTH60LHTB - ARTH54LHTA

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA, Zones, Master and RF as controlling sensor

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

Polarity is critical see below, for correct connection

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FFBDAD

Do

...

NOT use the terminal

...

Y1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  2 Y2 & 3 Y3 terminals in the Fujitsu FCU

...

...

  • Set this DIP switch (SW1) into the UP position

...

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ Y2 /

...

Y3: Connect the

...

Y2 /

...

Y3 cable from the Fujitsu FCU to

...

iZone CPU. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone

...