Fujitsu Compatibility: ARTG36LHTA - ARTG45LHTA - ARTG60LHTA - ARTG60LDTA

Panel
panelIconIdatlassian-note
panelIcon:note:
bgColor#C0B6F2

C320F & C325F have been superseded by C325F2

Current Firmware Version - 1.11

SERIES & kW

INDOOR

OUTDOOR

ARTG Series Wiring: Connect AC control cable to 2 and 3 - Polarity IS Critical

High Static Single Phase - Compact Outdoor

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

 

High Static Single Phase

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

ARTG54LHTC

 

High Static Infinity Range - Single Phase ONLY

ARTG45LDTA (single phase)

ARTG54LDTA (single phase)

ARTG60LDTA (single phase)

 

High Static Three Phase

ARTC72LATU

ARTC90LATU

 

ARTH Series Wiring: Connect AC control cable to Y2-Y3 and SW1 dip switch ON - Polarity IS Critical

only compatible with C325F2 v1.11 module

High Static Single Phase

ARTH60KHTA ( Single Phase )

 

Standard Range

ARTH54KHTA (Single phase)

 

High Efficiency

ARTH60KHTB (Single phase)

 

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA, Zones, Master and RF as controlling sensor

...

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#B3D4FF

Fujitsu Compatibility:

ARTH60LHTA - ARTH60LHTB - ARTHARTH54LHTA

Panel
panelIconIdatlassian-check_mark
panelIcon:check_mark:
bgColor#ABF5D1

Can use RA, Zones, Master and RF as controlling sensor

Panel
panelIconIdatlassian-warning
panelIcon:warning:
bgColor#FFF0B3

Polarity is critical see below, for correct connection

Panel
panelIconIdatlassian-cross_mark
panelIcon:cross_mark:
bgColor#FFBDAD

Do NOT use the terminal Y1 (12V) when connecting to an iZone system

...