1️⃣ The C150 can be installed on top of the indoor fan coil unit

2️⃣ If any wireless sensor (CRFS) or wireless bridge (CL5B or COCB) is not within the range of the C225 then additional repeaters (CR) should be added to help relay the signal from the field device to the C225 and the bridge

3️⃣ Do not run the blue network cables alongside 240 Volt wiring3️⃣

4️⃣ When installing network cables down wall cavities or chasing network cables into walls, tape up and protect the RJ45 connector to avoid damage to the connectors. Installation damage to cables is not covered under warranty

5️⃣ Always install zones in consecutive ports starting at Zone 1. The front of the C150 is marked with the zone port numbers

4️⃣ 6️⃣ Do not directly hard wire the CT24ACM into the AC unit’s power supply. This may void the warranty as it will require an electrician in the event that repair of the iZone 150 system is required

5️⃣ 7️⃣ Connect Zone Damper Actuators (CZDA) to the zone ports using the RJ12 cables as shown6️⃣

8️⃣ When installing temperature controlled zones ensure the sensors for the associated zone is installed in a location that is representative of the temperature in the room / zone . The sensor should be installed at approximately 1600mm above the floor and should not be subject to draughts, direct sunlight or heat from equipment such as computers, TV screens etc. The supply air outlets to this room must not blow conditioned air directly onto the sensors or CEPC

9️⃣ Connect the AC unit control cable to the C150 as per the instructions for your brand of AC unit

7️⃣ 1️⃣ 0️⃣ Remove the tabs on the CEPC batteries to activate power to the controller8️⃣

1️⃣ 1️⃣ Pair the CEPC to the C150, see here for a guide

1️⃣ 2️⃣ Only connect the power supply to the CT24ACM port after all components have been connected

1️⃣ 3️⃣ To access the C150 system via our iZone Home App, the building must be fitted with a compatible Wi-Fi modem. Contact iZone for a list of approved and recommended modems

1️⃣ 4️⃣ Any existing or new air conditioning units that require modification or additional boards to facilitate the correct operation of the iZone system, it is the responsibility of the installing contractor