Fujitsu Compatibility:

SERIES & kW

INDOOR

OUTDOOR

ARTG Series Wiring: Connect AC control cable to 2 and 3 - Polarity IS Critical

High Static Single Phase - Compact Outdoor

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

 

High Static Single Phase

ARTG30LHTA

ARTG36LHTA

ARTG45LHTA

ARTG54LHTC

 

High Static Infinity Range - Single Phase ONLY

ARTG45LDTA (single phase)

ARTG54LDTA (single phase)

ARTG60LDTA (single phase)

 

High Static Three Phase

ARTC72LATU

ARTC90LATU

 

ARTH Series Wiring: Connect AC control cable to Y2-Y3 and SW1 dip switch ON - Polarity IS Critical

High Static Single Phase

ARTH60KHTA ( Single Phase )

 

Standard Range

ARTH54KHTA (Single phase)

 

High Efficiency

ARTH60KHTB (Single phase)

 

Current Firmware Version - 1.10

Can use RA, Zones, Master and RF as controlling sensor

Polarity is critical see below, for correct connection

Do NOT use the terminal 1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  2 & 3 terminals in the Fujitsu FCU

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone

Fujitsu Compatibility:

ARTH60LHTA - ARTH60LHTB - ARTH54LHTA

Can use RA, Zones, Master and RF as controlling sensor

Polarity is critical see below, for correct connection

Do NOT use the terminal Y1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  Y2 & Y3 terminals in the Fujitsu FCU

  • Set this DIP switch (SW1) into the UP position

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ Y2 / Y3: Connect the Y2 / Y3 cable from the Fujitsu FCU to iZone CPU. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone