Haier Compatibility:

Current Firmware Version - 1.3

CODE

SENSOR TYPE

CONNECTION

C325HI2 v1.0

RA, Zones, Master, RF

A-B-C / Polarity Critical

SERIES & kW

INDOOR

OUTDOOR

AD100HN5FA-SET

10kW High Static Single Phase

AD100S2SH5FA

1U100S2SN5FA

AD125HP5FA-SET

12.5kW High Static Single Phase

AD125S2SH5FA

1U125S2SP5FA

AD125HN5FA-SET

12.5kW High Static Single Phase

AD125S2SH5FA

1U125S2SP5FA

AD140HP5FA-SET

14kW High Static Single Phase

AD140S2SH5FA

1U140S2SP5FA

AD160HP5FA-SET

15.5kW High Static Single Phase

AD160S2SH5FA

1U160S2SP5FA

Cannot use Zones, Master or RF as controlling sensor, RA ONLY

Polarity is critical see below, for correct connection

Requires Haier proprietary controller for setup - YRE-27

Requires Haier Interface board YCJ-A002

  1. Connect a shielded, 2 core, twisted pair control cable from the C225 / C325HI to the A / B terminals on the Haier Interface board YCJ-A002.

  2. Connect the interconnecting cable supplied by Haier to CN24 in the fan coil unit of the Haier Interface board YCJ-A002.

  3. Set the dipswitches as shown below. Polarity is critical.

  4. Haier YR-E17 wired RC must be connected and set to run on return air