Fujitsu Compatibility:
ARTG36LHTA - ARTG45LHTA - ARTG60LHTA - ARTG60LDTA
C320F & C325F have been superseded by C325F2
Can use RA, Zones, Master and RF as controlling sensor
Polarity is critical see below, for correct connection
Do NOT use the terminal 1 (12V) when connecting to an iZone system
Connect a shielded, 2 core, twisted pair control cable from the C225 / C325F2 to the 2 & 3 terminals in the Fujitsu FCU
1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling
2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical
3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone
Fujitsu Compatibility:
ARTH60LHTA - ARTH60LHTB - ARTH
Can use RA, Zones, Master and RF as controlling sensor
Polarity is critical see below, for correct connection
Do NOT use the terminal Y1 (12V) when connecting to an iZone system
Connect a shielded, 2 core, twisted pair control cable from the C225 / C325F2 to the Y2 & Y3 terminals in the Fujitsu FCU
Set this DIP switch (SW1) into the UP position
1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling
2️⃣ Y2 / Y3: Connect the Y2 / Y3 cable from the Fujitsu FCU to iZone CPU. Polarity is critical
3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone