Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 10 Next »

Fujitsu Compatibility:

ARTG36LHTA - ARTG45LHTA - ARTG60LHTA - ARTG60LDTA

C320F & C325F have been superseded by C325F2

Can use RA, Zones, Master and RF as controlling sensor

Polarity is critical see below, for correct connection

Do NOT use the terminal 1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  2 & 3 terminals in the Fujitsu FCU

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone

Fujitsu Compatibility:

ARTH60LHTA

Can use RA, Zones, Master and RF as controlling sensor

Polarity is critical see below, for correct connection

Do NOT use the terminal Y1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  Y2 & Y3 terminals in the Fujitsu FCU

  • Set this DIP switch (SW1) into the UP position

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ Y2 / Y3: Connect the Y2 / Y3 cable from the Fujitsu FCU to iZone CPU. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone

  • No labels