Mitsubishi Electric Compatibility:
Current Firmware Version - 1.0
Please note the dip switch settings for NEW ME R32 Gas Type models as indicated below.
SERIES & kW | INDOOR | OUTDOOR |
10kw - 14kw | PEA-M##GAA |
|
10kw - 14kw | PEA-M##HAA |
|
10kw - 14kw | PEA-M##JAA |
|
16kw (R32 Gas Type) | PEAM160HAAYKIT |
|
18kw (R32 Gas Type) | PEAM180LAAYKIT |
|
20kw (R32 Gas Type) | PEAM200LAA |
|
25kw (R32 Gas Type) | PEAM250LAA |
Can use RA, Zones, Master or RF as controlling sensor
Polarity is not critical
Take the Remote Controller (A / B) control wire from the fan coil unit and connect it to the AC Unit Control Cable on the C225 / C325M2
Please make sure to check the DIP SWITCH settings on the indoor unit board for NEW R32 Gas Type ME MODELS. DIP switch 8 on switch SW5 needs to be in the off position for both the old and the new modules to work.
1️⃣ Connect to A / B terminals: Connect wires to to A and B terminals. Polarity is not critical
2️⃣ Mitsubishi Electric FCU PCB
3️⃣ C225: iZone C225 module with C325M2 AC unit module connected
4️⃣ Shielded, 2 Core, twisted pair: This cable is not provided by iZone