1️⃣ The C110MC can be installed on top of the indoor fan coil unit
2️⃣ Do not run the blue network cables alongside 240 Volt wiring
3️⃣ When installing network cables down wall cavities or chasing network cables into walls, tape up and protect the RJ45 connector to avoid damage to the connectors
4️⃣ Always install zones in consecutive ports starting at Zone 1. The back of the C110MC is marked with the zone port numbers
5️⃣ Do not directly hardwire the CT24ACE into the AC unit’s power supply. This may void the warranty as it will require an electrician in the event that repair of the iZone 110 system is required
6️⃣ Connect Zone Damper Actuators (CZDA) to the zone ports using the RJ12 cables as shown
7️⃣ Connect the Wall controller(s) (C110WC) to the C110WC ports using the RJ45 cables
8️⃣ Only connect the power supply to the CT24AC port after all components have been connected
9️⃣ Initialise the system
1️⃣ 0️⃣ Configure the system
INITIALISE INSTRUCTIONS
All new or modified systems must be initialised prior to system configuration
To initialise the system press the button on the underside of any wall controller. This button is recessed so you will need to use a pen to press the button
The time to initialise the system will vary depending on the number of motors connected
The system will also initialise when power is restored after a power failure
CONFIGURATION INSTRUCTIONS
Only qualified iZone 110 installers should configure the iZone 110 System
Incorrect configuration could result in damage to your air conditioning unit and system
1️⃣ On the C110MC: Set the number of active zones required on the 6 position dip switch. By moving the associated dip switch up the respective zone will be deactivated and conversely by setting the dip switch down (ON), the associated zone will be activated
The factory setting is all 6 zones activated
2️⃣ On the C110MC: Set the number of electronic constants you require to ensure the safe operation of the system
An electronic constant is a safety feature and ensures that a predetermined number of zones remain open at all times even if all the zones are switched off.
If 1 electronic constant is selected, Zone 1 will automatically open if all the zones are closed. If 2 electronic constants is selected, Zone 1 and 2 will automatically open if all the zones are closed
Only set the number of electronic constants to 0 if the system is an old fashioned design with at least one supply air outlet that is not zoned
TESTING AND LABELLING
1️⃣ Set the AC unit fan speed to high and close all zones, now open one zone at a time and check which room the air is being supplied to
2️⃣ Label the zone using the stickers provided, being care full to place the sticker squarely in the recess provided