C110WC: Push Button - Install Guide
PAGE CONTENTS
PHOTO & DESCRIPTION
The C110WC is the user interface controller for the C110K system
Facia: The facia is moulded from ABS plastic and painted silver
Back casing: The back casing is moulded from ABS plastic and painted black
Wall Mounting plate (Not shown): The wall mounting plate is moulded from black ABS plastic. It can be fixed to the wall using the appropriate plugs and counter sunk screws. The Wall mounting plate will also fit onto a standard electrical wall box
Zone name: A pre-printed sticky labels are supplied with the C110WC. These should be peeled off and carefully stuck into the label recess
LED: The LED will illuminate blue we a zone is open and will turn off when the associated zone is closed
Silicon buttons: Press the associated zone button to open or close a zone
SPECIFICATIONS
Model numbers | C110WC |
Power supply | From C110MC module |
Power and communication connection | RJ 45 |
Communications protocol | RS 485 |
Operating Temperature | Room temperature |
Number of zones | 1 to 6 |
O/A Dimensions | Height 21 mm (Excludes RJ45 connector) Width 81 mm Length 122 mm |
Weight | 108 g |
WIRING DIAGRAM - C110WC
INSTALL INSTRUCTIONS
The C110MC can be installed on top of the indoor fan coil unit
Do not run the blue network cables alongside 240 Volt wiring
When installing network cables down wall cavities or chasing network cables into walls, tape up and protect the RJ45 connector to avoid damage to the connectors
Always install zones in consecutive ports starting at Zone 1. The back of the C110MC is marked with the zone port numbers
Do not directly hardwire the CT24ACE into the AC unit’s power supply. This may void the warranty as it will require an electrician in the event that repair of the iZone 110 system is required
Connect Zone Damper Actuators (CZDA) to the zone ports using the RJ12 cables as shown
Connect the Wall controller(s) (C110WC) to the C110WC ports using the RJ45 cables
Only connect the power supply to the CT24AC port after all components have been connected
Initialise the system
Configure the system
INITIALISE INSTRUCTIONS
All new or modified systems must be initialised prior to system configuration
To initialise the system press the button on the underside of any wall controller. This button is recessed so you will need to use a pen to press the button
The time to initialise the system will vary depending on the number of motors connected
The system will also initialise when power is restored after a power failure
CONFIGURATION INSTRUCTIONS
Only qualified iZone 110 installers should configure the iZone 110 System
Incorrect configuration could result in damage to your air conditioning unit and system
On the C110MC: Set the number of active zones required on the 6 position dip switch. By moving the associated dip switch up the respective zone will be deactivated and conversely by setting the dip switch down (ON), the associated zone will be activated
The factory setting is all 6 zones activated
On the C110MC: Set the number of electronic constants you require to ensure the safe operation of the system
An electronic constant is a safety feature and ensures that a predetermined number of zones remain open at all times even if all the zones are switched off.
If 1 electronic constant is selected, Zone 1 will automatically open if all the zones are closed. If 2 electronic constants is selected, Zone 1 and 2 will automatically open if all the zones are closed
Only set the number of electronic constants to 0 if the system is an old fashioned design with at least one supply air outlet that is not zoned
TESTING AND LABELLING
Set the AC unit fan speed to high and close all zones, now open one zone at a time and check which room the air is being supplied to
Label the zone using the stickers provided, being careful to place the sticker squarely in the recess provided