Fujitsu Compatibility: ARTG36LHTA ARTG45LHTA ARTG60LHTA ARTG60LDTA |
Panel | ||||||||
---|---|---|---|---|---|---|---|---|
| C320F & C325F have been superseded by C325F2||||||||
Current Firmware Version - 1.11 |
SERIES & kW | INDOOR | OUTDOOR |
ARTG Series Wiring: Connect AC control cable to 2 and 3 - Polarity IS Critical | ||
High Static Single Phase - Compact Outdoor | ARTG30LHTA ARTG36LHTA ARTG45LHTA |
|
High Static Single Phase | ARTG30LHTA ARTG36LHTA ARTG45LHTA ARTG54LHTC |
|
High Static Infinity Range - Single Phase ONLY | ARTG45LDTA (single phase) ARTG54LDTA (single phase) ARTG60LDTA (single phase) |
|
High Static Three Phase | ARTC72LATU ARTC90LATU |
|
ARTH Series Wiring: Connect AC control cable to Y2-Y3 and SW1 dip switch ON - Polarity IS Critical only compatible with C325F2 v1.11 module | ||
High Static Single Phase | ARTH60KHTA ( Single Phase ) |
|
Standard Range | ARTH54KHTA (Single phase) |
|
High Efficiency | ARTH60KHTB (Single phase) |
|
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Can use RA, Zones, Master and RF as controlling sensor |
...
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Do not NOT use the terminal 1 (12V) when connecting to an iZone system |
...
2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical
3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Fujitsu Compatibility: ARTH60LHTA - ARTH60LHTB - ARTH54LHTA |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Can use RA, Zones, Master and RF as controlling sensor |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Polarity is critical see below, for correct connection |
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
Do NOT use the terminal Y1 (12V) when connecting to an iZone system |
Connect a shielded, 2 core, twisted pair control cable from the C225 / C325F2 to the Y2 & Y3 terminals in the Fujitsu FCU
...
Set this DIP switch (SW1) into the UP position
...
1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling
2️⃣ Y2 / Y3: Connect the Y2 / Y3 cable from the Fujitsu FCU to iZone CPU. Polarity is critical
3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone
...