Fujitsu Compatibility:

ARTG36LHTA

ARTG45LHTA

ARTG60LHTA

ARTG60LDTA

C320F & C325F have been superseded by C325F2

Can use RA, Zones, Master and RF as controlling sensor

Polarity is critical see below, for correct connection

Do not use the terminal 1 (12V) when connecting to an iZone system

  • Connect a shielded, 2 core, twisted pair control cable from the  C225 / C325F2 to the  2 & 3 terminals in the Fujitsu FCU

1️⃣ iZone C225 module: Ensure the correct C325 module is connected for the AC unit make it is controlling

2️⃣ 2 / 3: Connect the 2 /3 cable from the Fujitsu FCU to here. Polarity is critical

3️⃣ Shielded cable: Shielded, 2 core, twisted pair cable must be used and is not supplied by iZone