C325 - Braemar
C325 - Braemar | For SDHV##D1S and KDHV##D1S series
C325 - Braemar | For KDHA###D1S series
For SDHV##D1S and KDHV##D1S series
Use C325B firmware version 1.3
SERIES & kW | INDOOR | OUTDOOR | Controlling sensor |
SINGLE PHASE / 7kw - 16kw | SDHV##D1S KDHV##D1S | SCHV##D1S KCHV##D1B | Can use RA as controlling sensor (not Zones/Master/RF) |
Requires Braemar proprietary controller for setup
Using XK60 or XK117
Unit in “OFF” state
Press “FUNCTION” & “TIMER” buttons for 5 seconds
Press “MODE” button to change “Function display” number
Press ▲ or ▼ button to change “Parameter display” number Press “ENTER/CANCEL” to save
Service Mode Parameter Table | |||||
Function Display | Function Description | Parameter Display | Parameter Description | ||
0 | Temp sensor location
Ensure set to '01'
| 01 | Sensor at return air for all modes | ||
02 | Sensor at wired control for all modes | ||||
03 | Sensor at return air for cool, dry & fan modes, at wired control for heat mode | ||||
10 | iZone control
Ensure set to '01' | 00 | Standard control | ||
01 | iZone control setting | ||||
11 | Indoor fan power setting
Factory default '05' Adjust to suit installed static Low static = '01' High static = '09'
|
| ESP (Pa) | High Speed | Low Speed |
01 | 10 | 5 | 1 | ||
02 | 20 | 6 | 2 | ||
03 | 30 | 7 | 3 | ||
04 | 40 | 8 | 4 | ||
05 | 50 (default) | 9 | 5 | ||
06 | 75 | 10 | 6 | ||
07 | 100 | 11 | 7 | ||
08 | 150 | 12 | 8 | ||
09 | 200 | 13 | 9 | ||
Using XK75
No adjustments need.
As per the instructions set the sensor to return air for all modes
Set the iZone control setting
Set the required static pressure setting
Cycle the power to the AC unit
Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit
Indoor fan coil unit PCB: Note connector CN1
Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical
C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated
Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector
Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided
For KDHA###D1S series
(GUD71~160PHS1/C-S introduced late 2024)
Use C325G3 module firmware 1.0
SERIES & kW | INDOOR | OUTDOOR | Controlling sensor |
SINGLE PHASE / 7kW - 16kW | KDHA###D1S | KCHA###D1B | Can use RA/Zones/Master/RF control |
Using XK75
1. As per the instructions set the sensor to return air for all modes
2. Set the iZone control setting
3. Set the required static pressure setting
4. Cycle the power to the AC unit
5. Connect a 2 core, twisted pair control cable from the C225 / C325G3 to H1/H2 in the fan coil unit
Polarity IS critical