C325 - Braemar

C325 - Braemar

C325 - Braemar | For SDHV##D1S and KDHV##D1S series

C325 - Braemar | For KDHA###D1S series

For SDHV##D1S and KDHV##D1S series

Use C325B firmware version 1.3

SERIES & kW

INDOOR

OUTDOOR

Controlling sensor

SINGLE PHASE / 7kw - 16kw

SDHV##D1S 

KDHV##D1S

SCHV##D1S 

KCHV##D1B

Can use RA as controlling sensor (not Zones/Master/RF)

Requires Braemar proprietary controller for setup

Using XK60 or XK117

Unit in “OFF” state
Press “FUNCTION” & “TIMER” buttons for 5 seconds
Press “MODE” button to change “Function display” number
Press ▲ or ▼ button to change “Parameter display” number Press “ENTER/CANCEL” to save

Service Mode Parameter Table

Function Display

Function Description

Parameter Display

Parameter Description

0

Temp sensor location

 

Ensure set to '01'

 

01

Sensor at return air for all modes

02

Sensor at wired control for all modes

03

Sensor at return air for cool, dry & fan modes, at wired control for heat mode

10

iZone control

 

Ensure set to '01'

00

Standard control

01

iZone control setting

11

Indoor fan power setting

 

Factory default '05'

Adjust to suit installed static

Low static = '01'

High static = '09'

 

 

 

 

 

 

ESP (Pa)

High Speed

Low Speed

01

10

5

1

02

20

6

2

03

30

7

3

04

40

8

4

05

50 (default)

9

5

06

75

10

6

07

100

11

7

08

150

12

8

09

200

13

9

Using XK75

XK75_steps.jpg

No adjustments need.

  1. As per the instructions set the sensor to return air for all modes

  2. Set the iZone control setting

  3. Set the required static pressure setting

  4. Cycle the power to the AC unit

  5. Connect a 2 core, twisted pair control cable from the C225 / C325B X / Y to CN1 in the fan coil unit

Indoor fan coil unit PCB: Note connector CN1

Connector and short cable provided: Insert the connector and short cable (see image below) into the connector CN1. Note the correct polarity for X & Y. Polarity is critical

C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN1 connector on the fan coil PCB and the C225 cable connector

Cable from CN1: Connect a shielded, 2 core, twisted pair cable to the connector and short cable provided

 

For KDHA###D1S series

(GUD71~160PHS1/C-S introduced late 2024)

Use C325G3 module firmware 1.0

SERIES & kW

INDOOR

OUTDOOR

Controlling sensor

SINGLE PHASE / 7kW - 16kW

KDHA###D1S

KCHA###D1B

Can use RA/Zones/Master/RF control

Using XK75

XK75_steps.jpg

1. As per the instructions set the sensor to return air for all modes

2. Set the iZone control setting

3. Set the required static pressure setting

4. Cycle the power to the AC unit

5. Connect a 2 core, twisted pair control cable from the C225 / C325G3 to H1/H2 in the fan coil unit

Polarity IS critical

H1-H2 Polarity Wiring.png