C325R/C325R2 - Rinnai

C325R/C325R2 - Rinnai

⚠️ IMPORTANT SAFETY NOTICE

DO NOT connect the AC unit control cable to the HA/HB (CN45) terminal on the indoor board if the unit is not listed as compatible for HA/HB connection. Incorrect connection will result in iZone CPU damage.

Rinnai Compatibility:

Current Firmware Version - 1.0

SERIES & kW

INDOOR

OUTDOOR

AC UNIT MODULE

DINLR XX Series only

 

 

C325R

DINLR XX A Series only

 

 

C325R2

Can use RA, Zones, Master or RF as controlling sensor

Polarity is critical see below, for correct connection

For HA/HB connection

Please refer to the information below for HA/HB connection details:

The unit models listed below require a minimum C225 firmware version 3.79 and the C325R2 AC unit module for operation

INDOOR

OUTDOOR

DINLR07B1A

DINLR09B1A

DINLR11B1A

DINLR13B1SA

DINLR15B1SA

DINLR15B1SA

DINLR18B1SA

DONSR07B1LA

DONSR09B1LA

DONSR11B1LA

DONSR13B1LA

DONSR15B1LA

DONSR15B1TA

DONSR18B1TA

  • A 2-core twisted pair control cable must be connected from the C225 / C325R2 controller to the HA/HB (CN45) port on the fan coil unit. The cable is supplied by iZone (CACUCM15). Connect the AC unit communication cable from the fan coil unit to the C225 as indicated below:

image-20260327-044133.png

For CN40 connection

For connection of older R410A fan coil units below:

Compatible Indoor Models

DINLR07Z72

DINLR10Z721

DINLR14Z72

DINLR17Z72

Compatible Indoor Models

DINLR07Z72

DINLR10Z721

DINLR14Z72

DINLR17Z72

  • Connect a 2 core + earth, twisted pair control cable from the C225 / C325R to the CN40 port on the fan coil unit. This cable is supplied by iZone - CACUCM15

CN40.jpg
Screenshot 2024-02-15 155548.jpg

 

Some Rinnai indoor units may have either of two connections: CN9 and CNXYE.

For CN9 connection

Connection for Three phase systems 20+kW.

Compatible Indoor Models

DINLR20Z7

DINLR24Z7

Compatible Indoor Models

DINLR20Z7

DINLR24Z7

CN9.jpg

 

Screenshot 2024-02-15 155316.jpg

For CNXYE Connection

Single phase R32 models 7-18 kW.

Compatible Indoor Models

DINLR07B1

DINLR09B1

DINLR11B1

DINLR13B1

DINLR15B1

DINLR18B1

Compatible Indoor Models

DINLR07B1

DINLR09B1

DINLR11B1

DINLR13B1

DINLR15B1

DINLR18B1

  • Connect a 2 core + earth, twisted pair control cable from the  C225 / C325R to the CNXYE port on the fan coil unit. This cable is supplied by iZone - CACUCM15

CNXYE.jpg
7b50a67b-87fe-437a-a2bf-4828a1e50db1.jpg

Indoor fan coil unit PCB

CN40: Connect to X and Y

C225 AC unit connector: Connect AC unit cable from fan coil to C225 as indicated

Polarity is critical: Make sure it is wired in accordance with these instructions on both the CN40 /CN9/CNXYE connector on the fan coil PCB and the C225 cable connector

Cable from CN40: Ensure the cable is shielded, 2 core, twisted pair. This cable is pre-terminated suitable for CN40 connector and is supplied by iZone

 

Resetting the Unit Addressing on Rinnai 20Kw+ units

When a Rinnai AC unit controller is used to do a test run, to put the iZone control system back on and operate the AC, unit addressing needs to be reset. Below is the procedure on how to do it.

  • First, make sure to cut the power to the indoor and outdoor unit both.

Off.png

 

  • Clear the indoor addresses by adjusting the S6 dip switch on OUTDOOR UNIT BOARD according to the photo:

    Dip switch ON-OFF.png

     

image-20240823-022015.png
  • Wait for 5 minutes, then turn both indoor and outdoor units back on.

On.png
  • Please wait another 5 minutes and turn it off again.

 

Off.png
  • Next, switch the unit to automatic addressing as shown below:

     

 

Dip switch ON-ON.png

 

 

IMG_3025.PNG

 

  • Now please power to the both indoor and outdoor back up

  • Connect iZone system back to the indoor unit and wait for 5 minutes.

  • You can run your AC by iZone system now.